Matexnet Limited - Delhi

37950447 auction sale of product 1 scrap ms heavy 2 ms scrap (light) 3 scrap conveyor belts above 5 mtr 4 scrap blow bar (sinter cast) 5 scrap oil filters (automobile) 6 xrfxray machine make philips (lab)pw160 7 ht motor 675 kw6.6 kva987 rpmmake kirlosker 8 lt motor with coupling 5.5 kw560 rpm14 amp415 volt make hindustan 9 lt motor with coupling 5.5 kw1460 rpm415 volt 10 ht motor 400 kw6.6 kv1490 rpmmake bhel 11 submersible pump set 0.75 kwtype self priming 1 ph 230 volt2900 rpmmakeshakti 12 battery charger pannel makebch 13 voltage transformer11kv110vmake cg 14 dg set with alternator engine with trolley set 5 kvamake crompton 15 dg set with alternator comp.set 250 kvamake cummins 16 lv breaker 415 volt rating 10004000 amp. make gec 17 hv breaker sf66.6 kva2500 ampmake abb 18 breaker control panel with protect relay ctpt. 19 dynamic breaking resistor (dbr) 27 kw1.35 ohmmake ohmark control ltd. 20 esp control panel ip360 vacop80 kv dcmodel ador corona 21 fly ash feeding control panel 80 tph415 voltmake trans weigh 22 fly ash feeding control panel 120 tph415 voltmake fls 23 control panel lubrication (gear box lubrication roller lubrication hydraulic lubrication) 415 v10 24 ups panel 30kvalp1030make aplab 25 dg synchronize panel with breaker 4 nos out going feeder415 volt1000 ampmakempact acv 26 liquid rotor starter (lrs) 2000 kwrotor voltage2133655 amp. 27 esp control panel rating110 kvdc600 mamakeador corona with controller (precisionii (cpp) 28 esp raper control panel make steller microtech with plc(allen bradley) cpp) 29 ups panel 40kva415 vac110vaccap42 ahmake hirel (cpp) 30 power supply panel with control card aux.transformer.rating 40 kvamake hirel (cpp) 31 scrap ewaste (cpudesktopprintercartridge etc) 32 scrap plotter printer oce colour wave 300t digital ...

Public Works Department - Delhi

37929178 tender for repair maintenance operation electrical and mechanical services at rao tula ram memorial hospital, jaffarpur, new delhi ( sh repairing and rewinding of burnt out main stator and rotor of kirloskar make alternator of 500kva dg set ) ...

Public Works Department - Delhi

37869218 repair maintenance of various electrical and mechanical services installed at dr. hedgewar arogya sansthan, karkardooma, delhi. sub head repairing of alternator of 625kva allied work in cummins make dg set...

Military Engineer Services - Delhi

37850831 comprehensive maintenance of dg sets and rep / maint of standby diesel engine prime powered alternator alongwith connected replacement of worn out spares filters / lubricant oil mccb / change over switches, contractors of amf panels in the area of age ( u ) e / s no iii under ge ( u ) electric supply delhi cantt 10...

Indian Coast Guard - Delhi

37850292 service rate contract for undertaking various routines on cummins diesel alternators and engines fitted on board icg ships and barges...

Indian Army - Delhi

37699706 bids are invited for ac filter , wiper blade , terminal plus ve , terminal ng ve , assy sleeve cyl , speedometer cable 3600 mm , separator fuel water cartridge , cartridge lubrication oil filter , solenoid switch fuel , wiper motor assy , fuel filter , stainer fuel , blinker glass lh , blinker glass rh , assy clutch master cyl , door lock frt lh , blinker transmitter , head light relay , front side indicator lh and rh 2.5 ton , 4 st relay 24 v , fuel water separator , wiper blade set , rear indicator assy lh and rh , door lock assy lh and rh , fog light assy , alternator 24v , bulb fog light head light indicator , element oil filter , mirror rear view set , clutch master cyl , head lamp rh and lh rhd 24 v set , combined stop and tail lamp , side indicator , clutch cyl repair kit , isolator switch , sprinkle motor sw , fuel filter cum water separator , pto pump fan belt total quantity : 159...

Indian Army - Delhi

37699365 bids are invited for boq mt shock absorber frt , shock absorber rear , clutch plate , wheel bearing frt , wiper blade , fuel filter , pressure plate , clutch master cyl , oil filter , head light relay , tail light assy , air filter , ac relay , ac filter , writing brush , car polish , car perfume , primary element air filter , assy oil filter , assy tandem master cyl , assy tail lamp lh side , assy wiper arm and blade lh side , assy wiper arm and blade rh side , rear door lock , head light assy lh , head light assy rh , power window switch , ac regulator sw , sprinkle motor , sprinkle nozzle , alternator total quantity : 127...

Indian Air Force - Delhi

37654256 procurement of spares for mirage 2000 aircraft => limited, 1 1 1497496 940ts09y01 panel alarm each 11 1f m2000 4 21 21 40 10 11 2 2 1497537 330ts07y204 radar power unit each 10 1f m2000 4 71 71 20 30 15 3 3 1520046 61057419 uap cots each 6 ipc 26 10 40 50 & 26 10 60 50 4 4 1505784 770905 1 0 conditioning control box each 6 1f m2000 4 20 20 11 60 10 5 5 1497495 990ts09y01 failure warning panel ( rear ) each 5 1f m2000 4 21 21 40 10 11 6 6 1497541 291bb01y04 04 armament interface box each 5 1f m2000 4 81 81 20 15 15 7 7 1497532 012079c01 throttle each 4 1f m2000 4 19 19 12 10 12 8 8 1553066 3511 135 61351 if am / fm each 4 ipc 26 10 40 50 & 26 10 60 50 9 9 1497501 742200 1 1 fuel monitoring panel each 4 1f m2000 4 26 26 51 10 11 10 10 1543710 742203 electronic components assembly each 3 ipc 26 10 40 50 & 26 10 60 50 11 11 1039494 959960712923 radio altimeter each 3 ipc 26 10 40 50 & 26 10 60 50 12 12 1508067 0203 0171 0011 lighting control box each 3 1f m2000 4 18 18 21 10 10 13 13 412215 06216320 01 circuit card assembly each 2 if4 65 66 1 06 14 14 1121255 p713914 alternator drains fitting each 2 1f m2000 2 02 wc 02 36 302 15 15 1497497 950ts09y00 panel, configuration each 2 1f m2000 4 15 15 30 30 10 16 16 1570140 gi4p9000 angle of attack probe each 2 1f m2000 4 61 61 20 10 10 17 17 1552938 eip585c rfc 585 each 1 ipc 26 10 40 50 & 26 10 60 50 18 18 1520048 45818580 filter block each 1 ipc 26 10 40 50 & 26 10 60 50 7 sd / signature of seller signature of buyer sd / ( shanta mishra ) wg cdr wg cdr proc te cell 12 may 23 19 19 1520049 62024622 dp wired structure each 1 ipc 26 10 40 50 & 26 10 60 50...

Indian Army - Delhi

37639654 bids are invited for ssl spares ssl 3c0492 link replacement set , 3c0046 steel track , 3c0047 rubber track , 3h0623 hydraulic pump assy , 10x0887 10x887 kit turbo charger , 3h0711 rear pump , 3c0198 hyd motor , 3h0710 front pump , 10x854 turbo charger , 3h0624 hydraulic motor , 10x0849 10x849 pump injector fuel , 3c0155 control valve , 3c0282 hyd cylinder , 3h0712 auxiliary pump , 3c0493 pin replacement set , 3c0003 bucket assy std , 10x0632 10x0635 motor starter , 3800939 engine oh set , 10x507 air heater starting , 3c0151 cyl assy , 10x0881 kit injector , 3c0122 cylinder liner , 3c0507 complete adj kit , 10x0758 pump water , 10x803 injector , 3c0126 complete cylinder , 10x0631 alternator , 10x0883 kit engine piston , 130000075 ripper tooth printed , 1z0129 quick hitch assy , 10x0888 kit water pump , 3d0056 chassis harness for skid steer , 3b0218 door assy complete , 10x0446 oil cooler core , 3a0028 radiator assy , 10x0445 radiator core , 3h0269 cabin lift assy , 3k0008 main shaft , 3j0229 door glass with frame , 3h0001 cylinder arm lift , 3c0195 pm2 pilot , 3c0191 hose with half inch iso qc female , 130000265 wheel spacer , 3c0107 connecting rod , 3d0057 cabin harness for skid steer , 10x0788 head fuel filter , 10x0790 level sensor , 3j0133 grill sheet rh , 3j0134 grill sheet lh , 3a0225 pump coupling , 3h0789 solenoid brake valve , 3h0882 flexible hose , 3c0171 cover , 3h0384 hose , 3a0133 fan , 3j0152 seat assy , 10x0473 body assy , nk12ssl fiber glass 02 03 , 3a0234 air cleaner , 10x669 gasket cylinder head , 3h0324 hydraulic filter assembly , 1f0009 rim , 3h0722 hose assy , 3j0185 front door glass , 3c0653 hose pipe , 10x0502 10x502 pressure switch , 3h0060 brake valve assy , 10x0821 ring piston , 10x0629 10x648 solenoid , 1 11310x0821 ring piston , 10x0629 10x648 solenoid , , 3h0199 spool assy , 3h0794 spool assy rh , 3h0725 hose assy , 130000115 element , 10x322 seal kit , 3a0227 relay , 340803 cable , 3c0166 flexible hose , 3c0163 quick coupling , 3c0176 flexible hose , 3c0094 bushing , 7079946210 bucket cyl seal , 10x868 10x867 valve intake , 10x740 exhaust valve , 130000163 brake seal kit vis 30 40 , 3h0764 hose assy , 3c0098 pin , 3h0803 auxiliary cable , 3c0137 joint kit , 3c0311 tooth straight , 10x725 pin, piston , 3h0220 control lever vertical assy , 10x866 spacer , 150101005 tool kit set , 3h0129 block assy , 3c0129 joint kit , 3b0249 engine cover top , 3b0239 engine cover bottom , 3c0156 m quick cupliing , 10x0781 tube injector , 10x0782 tube injector , 10x0783 tube injector , 1d0118 wper motor , 3c0165 flexible hose , 10x620 cartridge fule filter , 10x1022 spacer , 3c0160 flexbale hose , 3k0035 taper roller bearing id 60 , 3c0257 seal kit , 10x0454 element filter , 10x0703 gauge oil , 3c0159 flexible hose , 3j0058 control lever assy , 3d0008 fuel float tank unit , 3b0174 fuel float tank unit , 130000131 lever , 3c0070 pin , 3k0015 cover plate , 3c0154 flexible hose , 3k0016 cover hub , 10x0683 gasket , 10x0903 cabin cyl seal kit , 3h0768 hose , 3c0158 hose flexbile , 3k0034 taper roller bearing id 45 , 3c0175 spring , 10x856 gasket, front plate , 3h0774 hose assy , 3j0132 rear glass , 3d0010 hyd oil temp gauge , 3k0033 bearing 601342 ks , 3h0769 hose assy , 3b0178 lever assy , 10x0471 air filter element inner , 3j0141 front cab bush , 3c0161 flexible hose , 10x0501 3d0045 sensor water temp , 3h0657 hose assy , 3a0235 mounting bracket , 1d0039 fan , 10x0705 guide gauge , 3a0157 radiator bottom hose , 130000313 spring , 3d0007 hour meter , 3j0021 handle assy , 3h0145 control lever wa lh , 3k0009 sleeve , 10x453 hyd filter , 3h0767 hose , 3515254m1 hydraulic strainer , 3c0635 chain shield , 3c0092 ring nut , 3b0179 lever assy comp rh total quantity : 856...

Indian Air Force - Delhi

37614933 procurement of spares for rpa , carburator.as.1.3 , spiral antenna , dmrp assy , dfpc f / assy , gdd & demux , df antenna final assy , spa n / l , oil tank assy , carburator with new acd , electronic unit opats , mpw / exp x 335 final assy , video vmtrix , level sensor, fuel, metal, tubular, oal=372m , alternator without copling , pneumatic reservoir ( hr ) , oil radiator ( hr ) , intercooler ( hr ) , fod assy , msg pc , spa d / n , omni antenna assy , light taxi aircraft assy , sealed power supply 28vdc 100a system , hydraulic accumulator , dc / dc converter , lh land gear btp , elevator assy ( rh ) , shock absorber assy nlg mch , nose cover , horizontal tail assy ( including elevator ) , vertical tail assy left ( including rudder ) , vertical stabilizer rh / f / a , gdt uhf omni antenna , cable generator , cable generator...

Indian Air Force - Delhi

37614930 procurement of spares for mirage aircraft , o ring , corrosion preventive compound , gasket , o ring , o ring , gasket , switch, sensitive , relay , inflight refuelling light , stand by compass , structure, brake , extractor , box, inspection , box power supply , canopy hoisting sling , light emitting panel , light, recognition, aircraft , strap, webbing , valve , resistor, pyrometer , bevel ring , reflector light , relay electromagnetic , switch, toggle , fairing, alternator , door access , tee tube , mfs cable , cord assembly, electrical , cover access , ps sensor , bolt close tolerance...

Indian Army - Delhi

37536059 bids are invited for dozer bd 80 spares 116co12075 spring , 125pt03144 steering filter , 130ip91012 eng oil gauge , 125hs91637 seal oil , 125eg81458 horn switch , ceh0224120 horn , 116br01008 brake assy , 11z7181537 cartridge , 116fp11135 board floor , 31z11280155 air filter element , chs0700030 seal oil , 116cv00037 service kit , 116tf91576 ring span , 125hs02009 sight gauge , 31z1200272 element assy , 116eg91235 cable tacho hrs , 116co11743 disc , 110ec91146 strainer , 116tm92931 tube. , 116tm92923 tube , 116mc11656 cap , 30z8281061 solenoid 24v 4st , 110mc11286 lock , ctw0513641 de de spanner 36x41 , 116fp11127 board floor , 116fd11492 key , 30z1310046 gasket extn manifold , chh3005816 hose , cst0113243 sockt 32mm , cfs 01 31630 bolt , cfn1921411 nut , cfs0132045 screw key , 110mc02035 gauge lever , 30z1270113 gasket intake manifold , 116tf71585 1503013470 ring back up , 113eg91119 charge lamp , 116uj11121 bolt reamer , 125ad03025 pin and chain , cel2042411 lamp indicator eop , cfp0211438 pin , ctw0511011 spanner , ctw0514146 de de spanner 41x46 , cfn1942419 nut , 116fg11338 bolt , 116 hs 11803 spring , cfk0105010 key , 110tf11363 plug gresse disc , cfn4301219 nut , 116tm12424 plate , bfb3412063 bolt , cfb 07 21845 bolt , 30z1120482 gasket tappet cover , 116uj11024 needle , cfb0132050 bolt , cfs0132040 bolt , cel2042402 lamp indicator , 116fd61486 spacer , cfb0121065 bolt , cfw0112268 washer , cfb 07 21450 bolt , cfk0200722 key , cft0121640 stud bolt , cfs0131235 bolt , cfw0112060 washer spring , cft0331230 stud , 41z5181063 paper insert , cfw0112783 washer spring , cfs0131035 bolt , 116fg11402 shim 1.0 mm , cfw0111957 washer spring , 110eg81218 bulb , cfb0112060 washer spring , cfs0130825 screw , cfs0131025 screw , cfs2221020 screw , cfp0103220 pin cotter , cfw0211020 washer , cfw0111236 washer spring , 10z7180157 hose fip to filter , 110 mc 02019 disc , 440008029 feed pump assy , 0727101430 hose fip to return , 0727101435 hose fuel pipe , 0727101465 hose fuel , 0743411162 seal oil , 110fl91237 strainer , 110mc91136 seal oil , 116tfb0076 spring and cylinder assy , 116cob0037 rod and lever assy , 116ct61061 seai dust regular , 116ct91097 seal dust master , 116fd00111 transmission ser kit , 116fd02169 level gear and shaft a , 116fd51182 gear first , 116fg02096 cover engine side rh , 116fg02103 cover engine side lh , 116flb0034 strainer assy , 116hc01027 hyd cylinder assy lh , 116hs91362 stainer , 116mc00104 main clutch service kit , 116mc02098 main clutch housing assy , 116mc02146 inertia brake assy , 116mc02227 cover assy , 116mc41391 plate pressure , 116mc51492 shaft drive , 116mc71759 gasket , 116ph91006 hose , 116ps00104 steering strainer service kit , 116ps00112 steering piping service kit , 116ph00115 service kit , 116tf11596 ring , 116tfb0092 cyl assy , 116tfb0108 piston assy , 116tfb0132 bearing assy , 116tm02007 transmossion assy , 116tm03028 gear and pinion set , 116tm03036 gear driver 1st , 116tm03125 main shaft assy , 116tm03199 intermediat shaft assy , 116tm03214 gear shift fork assy , 116tm03222 gear shift lever assy , 116tm03247 lever assy e and r , 116tm11347 coller , 116tm11371 coller , 116tm11403 coller , 116tm11444 coller , 116tm11452 coller , 116tm11906 bolt joint , 116tm12157 shaft , 116tm51086 gear driven reverse , 116tm51742 gear driven fwd , 116tm51353 forward gear driven , 116tm71214 gasket , 116tm72227 gasket , 125fl02002 strainer , 30z3100016 crank shaft assy , 30z3180742 piston a type , 33z3100016 piston ring assy , 30z3210858 adaptor flywheel housing , 30z3280842 seal rear , 30z4170287 gasket tippet cover , 30z5181045 cartridge , 30z6200098 oil cooler , 30z7101522 feed pump assy , 31z1280114 valve evacuator , 31z1280188 hose turbo charger assy bd80 , 31z3280159 gasket k2 , 31z5170367 gasket lub pipe turbo , 31z7102168 30z7101871 , 31z8100096 turbo charger , 31z8201176 alternator assy , 31z5180743 oil filter cartridge , 31z9900265 cyl head gasket , 31z9900321 pto housing gasket kit , 375hc02018 piston seal , 41z8200687 alternator , 41z8380804 starter , cfk0105020 key , chs0113058 o ring , chs0113125 o ring , chs0115105 o ring , chs0112018 o ring , chs0113022 o ring , chs0113078 o ring , chs0115315 o ring , chs0115410 o ring , chs0710085 seal oil , cpf0600812 seal , chs0401015 gasket , cpf0600812 gasket , cfw0111030 washer spring total quantity : 2283...

Military Engineer Services - Delhi

37468921 tender for additional / alternator building no. p 33 ( kitchen for student offrs ) of iml new location under age b / r i and age e / m of ge ( south ) delhi cantt 10...

Indian Air Force - Delhi

37385765 bids are invited for procurement of 44 lines of dg set spares ring set piston , gasket exhaust pipe , water pump drive belt , alternator drive belt , oil filter , con rod bearing , seal for sump , washer injector , injector assy , clamp , gasket , fuel pipe solenoid valve , con rod bolt , stud , air cleaner , fuel pipe , screw , nut , hallow screw , fuel filter cartridge , hose , hose inter cooler , push rod , cylinder head gasket , joint , oil inlet pipe , exhaust manifold gaasket , gasket oil cooler , return pipe , circlip piston pin , oil section pipe gasket , connecting rod pipe , socket ring , hexagon bolt , hexagon nut total quantity : 205...

Central Public Works Department - Delhi

37265047 maintenance of various electrical and mechanical services of igi stadium, new delhi during 2022 23 ( sh: repairing and rewinding of alternator of 500 kva cummins make dg set at south plaza substation ) ...

Bharat Sanchar Nigam Limited - Delhi

36998546 supply of cluster 3a ( lakshadweep island ) . , item : cluster 3a ( lakshadweep island ) . , supply and erection of 40m ground based tower ( gbt ) including development of site, fencing in lakshadweep islandcluster 3a , supply and erection of 20m ground based tower ( gbt ) including development of site, fencing in lakshadweep islandcluster 3a , providing infrastructure as a service including supply, installation and commissioning of infrastructure items lithium ion battery, power plant, charging control unit ( ccu ) , engine alternator, solar panel system and subsequent operation &maintenance for 5 years of 4g gsmbss network for 37 sites of lakshadweep islandcluster 3a , operation & maintenance of of cable ( per km rate ) for 5 years...

Public Works Department - Delhi

36929241 up gradation / modification of substation equipment at jail no. 1, tihar jail, delhi 1 main lt panel 2 supplying, installation, testing & commissioning of cubical modular type lt panel suitable for 415 v, 3 phase, 4 wire 50 hz ac supply system fabricated in compartmentalized design having bus bar chamber duly fabricated from crca sheet steel of 2 mm thick for frame, back, sides, partition & doors and 3mm thick for glad plate duly powder coated in approved shade including cleaning & finishing complete with 7 tank process complete with2500 amp capacity extensible type four strip aluminium alloy bus bars of hight conductivity, dmc/ smc bus bar supports having short circuit withstand capacity of 31 mva for 1 sec., bottom base channel of ms section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common earth bar of size 25 mm x 5 mm at the rear with 2 nos. earth stud, solid connections from main bus bar to switch gears with required size of al. bus bars, control wiring with2.5 sq. mm. pvc insulated copper conductor single core cable, cooling / ventilation fans including construction of suitable cc foundation, in & out connections and providing & fixing following switch gears there in etc. complete as required. (i/c credit of dismantled panel to the agency) 3 incoming 4 (i) 2 nos 2000 ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 ka breaking capacity (ics = icu = icw=100%) for 1 second suitable upto 690v, fitted with interlocked door, automatic safety shutters, mechanical on/off and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc. complete with self powered microprocessor based release for adjustable setting for over current, earth fault & short circuit protection with lcd display & pre overload and over temperature protection indication & all other standard features conforming to is 1397 2 : 1993 as amended up to date(ii) 2 sets ryb phase indication led lamps with 6a, 10ka, c curve back up mcb, breaker on/off/trip indicating light with 6a, 10ka, c curve backup mcb(iii) 2 nos. 3 phase intelligent multifunction digital meter to read v, a, kva, kwh, pf hz etc. with 3 nos. resin cast cts of 2000/5 a class 1.0 accuracy and 15 va burden and with 3 nos 6a, 10ka, c curve back up mcb. 5 bus coupler 6 (i) 1 nos 2000 ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 ka breaking capacity (ics = icu = icw=100%) for 1 second suitable upto 690v, withoutrelease, fitted with interlocked door, automatic safety shutters, mechanical on/off and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc.(ii) 1 sets ryb phase indication led lamps with 6a, 10ka, c curve back up mcb, breaker on/off/trip indicating light with 6a, 10ka, c curve backup mcb. 7 interlocking 8 (i) electrical interlocking through advance contacts in acbs (all incomers & bus couplers)along with mechanical interlocking 9 outgoing 10 (i) 3 nos. 1600 ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 ka breaking capacity (ics = icu = icw=100%) for 1 second suitable upto 690v, fitted with interlocked door, automatic safety shutters, mechanical on/off and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc. complete with self powered microprocessor based release for adjustable setting for over current, earth fault & short circuit protection with lcd display & pre overload and over temperature protection indication & all other standard features conforming to is 1397 2 : 1993 as amended up to date.(ii) 3 sets ryb phase indication led lamps with 6a, 10ka, c curve back up mcb, breaker on/off/trip indicating light with 6a, 10ka, c curve backup mcb(iii) 3 nos. 3 phase intelligent multifunction digital meter to read v, a, kva, kwh, pf hz etc. with 3 nos. resin cast cts of 1600/5 a class 1.0 accuracy and 15 va burden and with 3 nos 6a, 10ka, c curve back up mcb.(ii) 10 set 630a, fp, 36ka mccb (ics=icu =100%)withmicroprocessor based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal. (iii) 10 sets on/offindicating light with 6a, 10ka, c curve backup mcb, auxiliary contacts with mccb 11 emergency panel 12 supplying, installation, testing & commissioning of cubical modular type lt panel suitable for 415 v, 3 phase, 4 wire 50 hz ac supply system fabricated in compartmentalized design having bus bar chamber duly fabricated from crca sheet steel of 2 mm thick for frame, back, sides, partition & doors and 3mm thick for glad plate duly powder coated in approved shade including cleaning & finishing complete with 7 tank process complete with2500 amp capacity extensible type four strip aluminium alloy bus bars of hight conductivity, dmc/ smc bus bar supports having short circuit withstand capacity of 31 mva for 1 sec., bottom base channel of ms section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common earth bar of size 25 mm x 5 mm at the rear with 2 nos. earth stud, solid connections from main bus bar to switch gears with required size of al. bus bars, control wiring with2.5 sq. mm. pvc insulated copper conductor single core cable, cooling / ventilation fans including construction of suitable cc foundation, in & out connections and providing & fixing following switch gears therein etc. complete as required. (i/c credit of dismantled panel to the agency) 13 incoming 14 (i)3 nos. 1600 ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 ka breaking capacity (ics = icu = icw=100%) for 1 second suitable upto 690v, fitted with interlocked door, automatic safety shutters, mechanical on/off and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc. complete with self powered microprocessor based release for adjustable setting for over current, earth fault & short circuit protection with lcd display & pre overload and over temperature protection indication & all other standard features conforming to is 1397 2 : 1993 as amended up to date(ii) 3 sets ryb phase indication led lamps with 6a, 10ka, c curve back up mcb, breaker on/off/trip indicating light with 6a, 10ka, c curve backup mcb(iii) 3 nos. 3 phase intelligent multifunction digital meter to read v, a, kva, kwh, pf hz etc. with 3 nos. resin cast cts of 1600/5 a class 1.0 accuracy and 15 va burden and with 3 nos 6a, 10ka, c curve back up mcb. 15 bus coupler 16 (i) 2 nos 1600 ampers four pole horizontal drawout type electrically operated air circuit breaker of fault breaking capacity 50 ka breaking capacity (ics = icu = icw=100%) for 1 second suitable upto 690v, withoutrelease, fitted with interlocked door, automatic safety shutters, mechanical on/off and service/test/isolated position indicators and frame earthing contact, auxilary contacts, shunt trip, interlocking features etc.(ii) 2 sets ryb phase indication led lamps with 6a, 10ka, c curve back up mcb, breaker on/off/trip indicating light with 6a, 10ka, c curve backup mcb 17 interlocking 18 (i) electrical interlocking through advance contacts in acbs (all incomers & bus couplers)along with mechanical interlocking 19 outgoing 20 (i) 3 sets 630a, fp, 36ka mccb (ics=icu =100%)withmicroprocessor based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal. (ii) 12 sets 400a, fp, 36ka mccb (ics=icu =100%)withmicroprocessor based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal. (iii) 8 sets 250a, fp, 36ka mccb (ics=icu =100%)withmicroprocessor based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal. (iv) 8 sets 200a, fp, 25ka mccb (ics=icu =100%)withthermal magnetic based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal. (v) 8 sets 160a, fp, 25ka mccb (ics=icu =100%)withthermal magnetic based release with adjustable settinghaving o/l & s/c protection with rotary handle and spreader terminal(vii) 39 sets on/off/ indicating light with 6a, 10ka, c curve backup mcb, auxiliary contacts with mccb. 21 bustrunking 22 supplying, installing, testing and commissioning of following capacity air insulated compact type bus trunking suspended on ceiling for use on 3 phase 4 wire 415 volts, 50hz a.c. supply with metal clad enclosure having ip 54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 nos aluminium bus bars having current density of 130 a/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints, fire barrier at each floor, continuous earthing with 2 nos aluminium strip of suitable size (one on each side) including, g.i. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. (i/c credit of the dismantled bus trunking to the agency) 23 dg set 24 providing, installing, testing and commissioning of ‘silent type’ diesel generating set alongwith having prime power rating of 1010kva, 415 volts at 1500 rpm, 0.8 lagging power factor at 415 v suitable for 50 hz, 3 phase system & for 0.85 load factor, is/iec 60034 1,is 1460, iso 8528, iso 3046, is 13018, iso 9001 standards and consisting of the followings: (i/c credit of dismantled 380kva dg set to the agency) 25 diesel engine: 26 diesel engine 4 stroke water cooled, electric start, of suitable bhp at 1500 rpm suitable for above output of alternator at 40 degree c, 50% rh & at 1000 meter msl and conforming to iso 3046, capable of taking 10% over loading for one hour after 12 hours of continuous operation. the engine will be fitted complete with all the required accessories. 27 engine mounted instrument panel fitted with and having digital display for following: (i) start stop switch with key (ii) water temperature indication (iii) lubrication oil pressure indication (iv) lubrication oil temperature indication (v) battery charging indication (vi) rpm indication (vii) over speed indication (viii) low lub. oil trip indication (ix) engine hours indication 28 alternator : 29 synchronous alternator rated at1010kva, 415 volts at 1500 rpm, 3 phase 50 hz, ac supply with 0.8 lagging power factor at 40 degree c, 50% rh & at 1000 meter msl. the alternator shall be having spdp enclosure, brushless, continuous duty, self excited and self regulated through avr conforming to is/iec 60034(i) suitable for tropical conditions and with class f/h insulation. 30 base frame & foundation: 31 both the engine and alternator shall be mounted on suitable base frame made of ms channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. 32 fuel tank: 33 daily service fuel tank of 990 liters capacity fabricated out of 3 mm thick m.s. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with ms class ‘c’ pipes of suitable dia. complete with valves, level indications & accessories as required as per specifications. 34 exhaust system: 35 dry exhaust mainfold with hospital exhaust silencer and catalytic convertor. 36 starting system: 37 12v/24v dc starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 180 amp. hour capacity lead acid type) as required as per specifications. 38 accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. 39 amf panel 40 fabricating, installing, testing & commissioning of automatic mains failure control including auto by pass panel, suitable for 1010 kva silent type dg set complete with relays, timers, set of cts for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, kwh, kvarh & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from amf panel to diesel engine and elsewhere if required, all complete and interlocking including the following: (i/c credit of dismantled amf panel to the agency) 41 (a) 02nos. 1600amp., motorised electrically operated draw out with cradle type 3 position acb with microprocessor based release for o/c & e/f and shunt trip. 42 (b) auto/manual/test/off selector switch 43 (c) 2 nos. over voltage relay, 2 nos. reverse power relay and 2 nos. under voltage relay. 44 (d) 3 sets of current transformers 15 p 10 accuracy for protection and 15 va class i for metering 45 (e) energy analyser unit to indicate current voltage frequency power factor and kwh 46 (f) indicating lamps for load on mains and load on set 47 (g) fuse for instruments 48 (h) battery charger, complete with transformer/ rectifier, d.c. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment. 49 (i) main supply failure monitor 50 (j) supply failure timer 51 (k) restoration timer 52 (l) control unit with three impulse automatic engine start/stop and failure to start lockout. 53 (m) impulse counter with locking and reset facility. 54 (n) on/off/control circuit switch with indicator 55 (o) audio/video annunciation for (i) high water temperature (ii) low lubricating oil pressure (iii) engine over speed (iv) engine fails to start (v) full load/maximum load warning 56 earthingearthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. 57 providing and fixing 25 mm x 5 mm copper strip in 40 mm dia g.i. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re filling etc. as required. 58 earthing with g.i. earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. 59 providing and fixing 25 mm x 5 mm g.i. strip in 40 mm dia g.i. pipe from earth electrode including connection with g.i. nut, bolt, spring, washer excavation and re filling etc. as required. 60 cablesupplying & fixingof following size xlpe insulated and pvc sheathed aluminium conductorarmoured power cable of 1.1 kv grade conf. to is 7098 (part i)in the following ways etc complete as required. 61 3.5 x 185 sq.mm 62 3.5 x 120 sq.mm 63 3.5 x 95 sq.mm 64 3.5 x 50 sq.mm 65 supplying and making end termination with brass compression gland and aluminium lugs for following size of pvc insulated and pvc sheathed / xlpe aluminium conductor cable of 1.1 kv grade as required. 66 3½ x 185 sq. mm (57mm) 67 3½ x 120 sq. mm (45 mm) 68 3½ x 95 sq. mm (45 mm) 69 3½ x 50 sq. mm (35 mm) 70 misc. civil workproviding and laying in position cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, dg set etc. including form work etc. as required. 71 excavation of the cable trenches in hard rock not exceeding1.5 meter in width, and lift upto 1.5 meter, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 meter. 72 providing brick work (in width 225 mm or more) with f.p.s. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. 73 providing 15 mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels. 74 demolishing of existing wall i/c reparing with cement plaster and dispose of excavated malba at suitable place out of the site. ...

Public Works Department - Delhi

36929058 repair maintenance of electrical and mechanical services at rao tula ram memorial hospital, jaffarpur, new delhi ( sh repairing and rewinding of burnt out main stator and rotor of kirloskar make alternator of 500kva dg set ) ...

Ministry Of Defence - Delhi

36842396 bids are invited for mtstores mudflap cat part no 2222347599 , cross member cat part no 2222382932 , shock absorber cat part no 2222516093 , shock absorber cat part no 2222516094 , starter motor cat part no 2222625163 , fuil filter cat part no 2222662637 , door panel cat part no 2282502754 , door panel cat part no 2285502755 , fuel pipe cat part no 2221888187 , oil filter cat part no 2221913336 , hose assembly cat part no 2222660861 , cross membr cat part no 2222382921 , bumper cat part no 2282617901 , radiator hose cat part no 2221743135 , air cleanaer cat part no 2221743197 , muffler cat part no 2222020737 , alternator cat part no 2222358537 total quantity : 30...

Indian Army - Delhi

36756206 bids are invited for mt stores mudflap cat part no 2222347599 , cross member cat part no 2222382932 , shock absorber cat part no 2222516093 , shock absorber cat part no 2222516094 , starter motor cat part no 2222625163 , fuil filter cat part no 2222662637 , door panel cat part no 2282502754 , door panel cat part no 2285502755 , fuel pipe cat part no 2221888187 , oil filter cat part no 2221913336 , hose assembly cat part no 2222660861 , cross membr cat part no 2222382921 , bumper cat part no 2282617901 , radiator hose cat part no 2221743135 , air cleanaer cat part no 2221743197 , muffler cat part no 2222020737 , alternator cat part no 2222358537 total quantity : 30...

Northern Railway - Delhi

36708082 auction sale of cond and scrap all type of electric motor fitted with or without pully, blower motor, condensor motor, electric alternator motor , alternator, mono block pump, different sizes and different make, and different hp. with n / f attachment, sort and sizes, burnt, broken and unbroken, as is where is basis, as it is.note: loading by purchaser...

Bharat Sanchar Nigam Limited - Delhi

36683333 cluster 2a ( assam, west bengal and sikkim ) , items : cluster 2a ( assam, west bengal & sikkim ) , supply and erection of 40m ground based tower ( gbt ) including development of site, fencing inassam, west bengal & sikkimcluster 2a , supply and erection of 20mground based tower ( gbt ) including development of site, fencing in assam, west bengal & sikkimcluster 2a , providing infrastructure as a service including supply, installation and commissioning of infrastructure items lithium ion battery, power plant, charging control unit ( ccu ) , engine alternator, solar panel system and subsequent operation &maintenance for 5 years of 4g gsmbss network for 578 sites of assam, west bengal & sikkimcluster 2a , operation & maintenance of of cable ( per km rate ) for 5 years...

Bharat Sanchar Nigam Limited - Delhi

36683324 cluster 1a ( meghalaya, tripura and mizoram ) , items : cluster 1a ( meghalaya, tripura & mizoram ) , supply and erection of 40m ground based tower ( gbt ) including development of site, fencing inmeghalaya, tripura & mizoram cluster 1a , supply and erection of 20m ground based tower ( gbt ) including development of site, fencing inmeghalaya, tripura & mizoram cluster 1a , providing infrastructure as a service including supply, installation and commissioning of infrastructure items lithium ion battery, power plant, charging control unit ( ccu ) , engine alternator, solar panel system and subsequent operation &maintenance for 5 years of 4g gsmbss network for 572 sites of meghalaya, tripura & mizoram cluster 1a , operation & maintenance of of cable ( per km rate ) for 5 years...

Indian Army - Delhi

36522033 bids are invited for ( a ) 24136 / dp384 / 22 23 lv7 / sml lp01 24 x15 drive assy ( lucas ) nos 200 ( b ) 24136 / dp385 / 22 23 lv7 / tmb 2751 1540 0121 drive assy nos 181 ( c ) 24136 / dp386 / 22 23 lv7 / sml lpx3 18 300 alternator 12v / 55amp nos 13 ( d ) 24136 / dp387 / 22 23 lv7 / sml lp01 24 z12 stator assy nos 34 ( e ) 24136 / dp388 / 22 23 lv7 / sml lp26 18 300 alternator 135 amp nos 11 ( f ) 24136 / dp389 / 22 23 lv7 / tmb 2841 8240 9901 wiper motor 17w, 12v nos 06 ( g ) 24136 / dp390 / 22 23 lv7 / tmb 2621 3964 stator winding assy nos 46 ( h ) 24136 / dp391 / 22 23 lv7 / sml lp01 24 x18 field coil assy nos 490...

Ministry Of Defence - Delhi

36461685 bids are invited for demand of store mse steering cover grey , carpet floor mat set standard , feel leather seat cover ciaz , shaft counter maruti van , valve egr sx4 , body assy throttle ciaz sx4 , charger assy turbo sx4 , senser air pressure ciaz , muffler comp ciaz , sporket assy camshaft ciaz , pully crankshaft ciaz , belt water pump sx4 ciaz , tie rod end maruti van , assy return pipe car amb , shaft counter maruti van , gear complete primary drive mc , alternator assy for car amb , valve assy air suction mc , rear hub assy mc , cly head with stud mc hh , cly head with stud mc re , drum kit riso mc , muffler complete exhaust mc , carpet floor mat set standard , cotton waste for cleaning prupose , distilled water for batteries , feel leather seat cover eicher maruti van , lifter assy mc total quantity : 562...

Indian Army - Delhi

36252730 bids are invited for jcb spares gear box assy of jcb , turbo charger of jcb , excavator valve of jcb , blade back of jcb , radiator of jcb , radiator aluminium of jcb , combination switch of jcb , prop shaftof jcb , bucket of jcb , valve solenoid of jcb , kit spider of jcb , coil of jcb , kit seal main hyd pump of jcb , air filter outer of jcb , rear rim of jcb , hub planetary of jcb , solenoid valve assy of jcb , element transmission filter of jcb , abi exhaust silencer turbo of jcb , bucket ram seal kit of jcb , kit brake pads of jcb , air filter inner of jcb , hydraulic oil filter of jcb , tool kit of jcb , thermostat element of jcb , lead bty positive of jcb , boom ram seal kit of jcb , lead battery negative of jcb , micro starter of jcb , silencer exhaust turbo of jcb , air cleaner element main outer pc of jcb , element fuel sediment fillter catridge of jcb , fuel filter of jcb , joint for rocker cover of jcb , fuel filter element of jcb , alternator of jcb , piston bearing of jcb , unloader valve with tyre inflator of jcb , switch panel head lamp of jcb , flap front of jcb , bearing of jcb , grommet cable harness of jcb , flap rust of jcb , wiper blade of jcb , plunger of jcb , strut gas window of jcb , air filter of jcb , pump lift of jcb , tail lamp indicator left of jcb , tail lamp indicator right side of jcb , inner latch assy lh of jcb , glass tinted left side of jcb , seal kit of jcb , glass front qtr light lh clear of jcb , glass frt qty light clear of jcb , glass six lights of jcb , bearing liner of jcb , switch oil pressure engine of jcb , starter relay of jcb , l h side window glazing surround of jcb , window handle lh of jcb , radiator bottom hose of jcb , radiator top hose of jcb , door tinted glass lower of jcb , ball of jcb , hose soc main hyd pump of jcb , ignition switch of jcb , liner bearing of jcb , throttle cable of jcb , window tinted glass rh of jcb , seal window rh of jcb , grommet of jcb , gasket of jcb , grommet small of jcb , o ring od of jcb , grease bleed nipple cap of jcb , cap screw of jcb , bulb of jcb , o ring of jcb , spanner de of jcb , bearing self lub of jcb , fuel filter of jcb , screw of jcb , bolt of jcb , dowel of jcb , seal of jcb total quantity : 479...

Northern Railway - Delhi

36168529 supply of grease shell gadus rail s2 traction motor bearing grease of bharat shell ltd or servo plex tm3 of iocl or balmerol multigrease tm3 of balmer lawrie for traction motor / generator / alternator sealed bearings of alco, dlw diesel electric locos. nb: ( 1 ) firm other than oem need to be submit tender specific authorisation otherwise offer will be rejected straightway. ( 2 ) no product other than mentioned in rdso latest mp.mi 15 for usage mentioned is acceptable. [ warranty period: 30 months after the date of delivery ] dsl / cb , nr uttar pradesh 1758.00 kg dsl / ldh , nr punjab 586.00 kg...

Delhi Transco Limited - Delhi

36167197 tender for annual maintenance contract (amc) and supply of necessary material for 30kva dg set at 220kv sub station gazipur under sr. mgr(t) o&m e 5 1 k oil,super,dg, kbl,rb66 02 ea 2 lub oil filter,30kva,dg set 02 ea 3 fuel filter kit,30kva,dg set 02 ea 4 belt for blower,30kva,dg set 02 ea 5 belt for dc alternator,30kva,dg set 02 ea 6 rocker cover,30kva,dg set 02 ea 7 amc of 30kva, dg set (complete servicing, overhauling etc.) 04 ea 8 freight charges 01 ea...

Northern Railway - Delhi

36068685 supply of suspension hanger pin & split cotter for 25kw transom mounted alternator as per rdso drg no. skel 3943, ( rev 1 ) 2012. [ warranty period: 30 months after the date of delivery ] ...

Indian Army - Delhi

35843049 bids are invited for engine assy 6 bt aa 5.9 130 hp bs iii engine complete with 3rv liner, alternator 24 v 75 amps, starter motor, air compressor turbocharger, fuel filter & fuel lines, water colling lines suitable for g 600 gear box & without clutch 352 dia & clutch housing...

Container Corporation Of India Limited - Delhi

35836577 enquiry for procurement of following engines spares for hyster make rsts at icd tkd => limited fngire eledrocuc control module ( programmed ) pno.cummnms 43091759111 1 p no 1sa8236 rep 1588263r hyster i engini iemperature sensor ( ntake 2 mawifoud ) pno 1s1s831 hysrer i cummins p.no 3085198 i 3o8sir8 fuel injectorpn hi612812 / cummins 3 p.no 4903472 • belt tensioner pulley compressor 4 p.no17o8392hystericumuinspno 3102888 engine ol pressure sensor ( oil pressure 8 oil temperature ) p no 1663000 hystericummins p no 4g21477 engine pulley p, no 1708389 iiysterui 6 cumminspno 3o99205 water pump mount [ ng seal pno 7 1708382 hyster i cummins p.no 2863701 alternator belt tensioner pno 8 4015344 hyster / cummins p no 3691280...

Indian Army - Delhi

35813920 bids are invited for alternator starter test bench total quantity : 1...

Northern Railway - Delhi

35666970 supply of grease shell gadus rail s2 traction motor bearing grease of bharat shell ltd or servo plex tm3 of iocl or balmerol multigrease tm3 of balmer lawrie for traction motor/ generator/alternator sealed bearings of alco, dlw diesel electric locos.grease shell gadus rail s2 traction motor bearing grease of bharat shell ltd or servo plex tm3 of iocl or balmerol multigrease tm3 of balmer lawrie for traction motor/ generator/alternator sealed bearings of alco, dlw diesel electric locos.,grease shell gadus rail s2 traction motor bearing grease of bharat shell ltd or servo plex tm3 of iocl or balmerol multigrease tm3 of balmer lawrie for traction motor/ generator/alternator sealed bearings of alco, dlw diesel electric locos. nb:(1) firm other than oem need to be submit tender specific authorisation otherwise offer will be rejected straightway. (2) no product other than mentioned in rdso latest mp.mi 15 for usage mentioned is acceptable. [ warranty period: 30 months after the date of delivery] dsl/cb , nr uttar pradesh 1820.00 kg dsl/ldh , nr punjab 546.00 kg...

Public Works Department - Delhi

35605319 tender for repair maintenance of e and m service at ludlow castle wrestling venue 49 sham nath marg and directorate of education delhi ( sh routine maintenance of dg sets ) sub head i ( 49 sham nath marg & directorate of education ) annual service maintenance contract of following capacity d.g. set complete with alternator amf panel & battery charges i / c carrying out the periodic maintenance and with 2 nos. b check kits of each generator in a year along with material to be supplied required for the b check. the material to be supplied & other terms & conditions are as under: a ) 125kva dg set 2nos. ( installed at directorate of education delhi, and at directorate of agriculture marketing 49 sham nath marg. ) ( cummins make ) 1.separator fuel water ( part no.4093731 ) 4 pcs.2.filter fuel ( part no. 3931063 ) 4 pcs.3.cartridge lub oil filter ( part no.3977743 ) 4 pcs.4.inhibitor corrosion 5 liters ( part no.3816986 ) 4 pcs.5.foil sealed test strips cc2602b ( part no.3403800 ) 4 pcs.6.indicator restriction ( part no.3872813 ) 4 pcs.7.kit air cleaner elements ( part no.3238666 ) 2 pcs.8.gasket rocker lever cover ( part no.3930906 ) 12 pcs.9. premium blue 7800 plus 1 / 20 ltr ( part no.505441 ) 4 pcs. 2 sub head ii ( 9 sham nath marg honble speaker residence ) annual service maintenance contract of following capacity d.g. set complete with alternator amf panel & battery charges i / c carrying out the periodic maintenance and with 2 nos. b check kits of each generator in a year along with material to be supplied required for the b check. the material to be supplied & other terms & conditions are as under: a ) 25 kva dg set 1 job. ( cummins make ) .1.filter oil ( part no.0122 0922 ) 2 pcs.2.filter fuel ( primary ) ( part no.0149 2827 ) 2 pcs.3.filter fuel ( secondary ) ( part no.0149 2828 ) 2 pcs.4.inhibitor corrosion 5 liters ( part no.3816986 ) 2 pcs.5.foil sealed test strips cc2602b ( part no.3403800 ) 2 pcs.6.element air cleaner ( part no.0140 4088 ) 1 pcs.7. indicator service restriction ( part no. 0140 4213 ) 1 pcs.8.premium blue 7800 plus 1 / 10 ltr ( part no.506924 ) 2 pcs. 3 sub head iii ( ludlow castel ) comprehensive maintenance of 320 kva dg setcomplete with alternator, amf panel & battery charger i / c carrying out the periodic maint & with b check kits of each generator in one year along with material to be supplied required for the b check. and all other materials required for all relevant checks recomended & as per specification of oem etc, as reqd & other terms & conditions are as under ( the following parts shall be changed after each six month or 250 hrs. which is comes earlier ) 2 nos. ( cummins make dg set ) 1. element lube oil filter ( part no. 3238204 ) 4 pcs.2. kit fuel filter and ring ( part no. 3238493 ) 4 pcs.3. kit super bypass filter ( part no. 3879488 ) 4 pcs4. seal o ring ( part no. 3010937 ) 4 pcs5. inhibitor corrosion 5 liters ( part no. 3167217 ) 4 pcs6. strip test ( part no. 4912590 ) 4 pcs7. indicator restriction ( part no.3872813 ) 4 pcs8. kit air cleaner element ( part no.3238358 ) 2 pcs9. gasket rocker lever cover ( part no.4072426 ) 6 pcs10.premium blue 7800 plus 1 / 20 ltr ( part no. 505441 ) 8 pcs...

Military Engineer Services - Delhi

35583751 repair / maintenance of dg sets of various capacities, servicing and maint of eot crane and repair / maintenance of sewage pumps, sewage treatment plant and connected misc e / m items / works at anand parbat mil stn under ge ( north ) delhi cantt 10. comprehensive maintenance of dg sets & amf panel of make as mentioned against each dg sets below including preventive maintenance checks of engine and alternator for trouble free function as per recommendation and attending break down / complaint as and when on required basis, monthly maintenance on regular basis complete with preventive maintenance ( b check ) twice a year including replacement of engine oil / coolant, replacement of required necessary spares and replacement of all types of filters, belts along with rectification of minor defects and cleaning of air filters / breather, coolant tank with blower and labour for filling / topping up and tuning of engine for dg set as listed below complete all as specified and directed. note : the rates quotedagainst for ser item no 1.01 to 1.07items shall be applicable for a period of 01 month. 2 40 kva dg set 01 nos ( location: ranjith hall, make: crompton greaves ) 3 62.5 kva dg set 01 nos ( location: bapa nagar pump house, make: kirloskar ) 4 62.5 kva dg set 01 nos ( location: map ph ii pump house, make: greaves power ) 5 100 kva dg set 01 nos ( location: map ph i pump house, make: jackson / kirloskar ) 6 125 kva dg set 01 nos ( location: amar vihar, make: greaves / kirloskar ) 7 160 kva dg set 01 nos ( location: klp area, make: cumins / stamford ) 8 200 kva dg set 03 nos ( location: deepak vihar, make: greaves power ) 9 notes: ( a ) after monthly maintenance, the work to be certified by je ( e / m ) / engr in charge on job card. ( b ) cost of materials and labour as mentioned in below are not included with comprehensive maintanance. ( c ) the comprehensive maintenance of work shall be done through respective oems or their authorised dealers. ( d ) the contractor shall carry outroutine checking of the complete dg sets and rectify the minor / major defects noticed immediately.if complaints were not attended within one hours a penalty of rs 500 per fault per hour shall be imposed over contractor and shall be deduct from his dues. ( e ) contractor has to carry out monthly maintenance with examination of suction and exhaust valves for smooth operation of dg sets. ( f ) contractor shall be responsible to monitor the followings of alldg sets during comprehensive maintenance andthe cost of same is deemed to be included in the quoted rate: ( i ) examination and cleaning of fuel injection, nozzles. ( ii ) check clearance of suction and exhaust valves and adjust if required, ( iii ) changing of oil filters, fuel filters screen filters assy. ( iv ) maintenance of coolant level all as directed by the engineer in charge. ( v ) change of hydraulic governor oil ( vi ) change of oils ( vii ) clean alternator winding in position by forced air and internal surfaces lubricate de & nde bearings ( viii ) tightining of all nut bolts. ( ix ) greasing of all points. ( x ) test ir value of alternator winding and recording the readings ( xi ) checking of any leaking in fuel & oil lines and rectification of the same. ( xiii ) any other check as reqd for efficient running of equipment all as specified & directed by engr in charge. ( xiv ) the rates quoted against the above mentioned items is deemed to be included for cost of labour, cost of t & p requiredfor replacement of unserviceable parts and cost of handling / transportation of defective item to & from civil workshop for repair if required. spares shall be measured and paid separately under respective items.supply only items labour cost is deemed to be included in this item. ( xv ) in case of break down, the additional manpower if required will be arranged by the contractor. the cost of the same are deemed to be included in the quoted rate. 10 supply only in replacement of v belts for radiator fan / main shaft / cam shaft for the dg set of capacity 40 kvato 200kva as per existing size and model complete all as specified and direceted. 11 supply only in replacement of fuel filters for the dg set of capacity 40 kva to 200kva as per existing size and model complete all as specified and direceted. 12 supply only in replacement of oil lub filters for the dg set of capacity 40 kva 200kva as per existing size and model complete all as specified and direceted. 13 supply only in replacement of air filters for the dg set of capacity 40 kva 200kva as per existing size and model complete all as specified and direceted. 14 supply only in replacement of lubricant oil ( 15w40 ) for the dg set of capacity 40 kva 200kva as per existing size and model complete all as specified and direceted. 15 supply only in replacement of coolant for the dg set of capacity 40 kva 200kva as per existing size and model complete all as specified and direceted. 16 s&f in repairs rewininding with super enamelled copper wire of existing size & insulating the field coil assembly, replacing bentec assembly ofthe self starter assembly 12 / 24 voltsand refixing the same after repairs andtesting complete all as specified. 17 s&f in replacement ofself starter assembly 12 / 24 volts existing size and model andtesting complete all as specified. 18 s&f in repairs lead acid batteries of 12 volts, 110 150 ah, 22 28 plates, maintenance free type including accesories like terminal clamps, copper cable of required size and length, petroleum jelly and baterry initial charging all as specified and as directed. make exide / amar raja / luminious / hbl 19 s&f in repairs battery charger capacity 6 / 12 amp, 12 / 24 voltsfor dg set complete all as specified and directed. 20 m&l for carring out repairs to 12 / 24volt dynamo by replacement of carbon brush, electronic regulator, rectifier, windings, bearings reassembling the same and testing complete all as specified and directed. 21 s&f in replacement aganist repairs of stop solenoid / shut off valve of capacity 40 to 200 kva dg sets of existing make along with screen filterincluding wiring connecting to panel circuit, starting and testing on load complete all as specified and directed. 22 s&f in repairs of thermostat element alongwith complete assy for dg set connection and testing complete all as specified and directed. 23 m&l for repairs and calibration of pt fuel pump as per the calibration procedure and norms as per manufactures guide linesfor dg set of various capacity from40 to 200kvaincluding replacement of worn out and unserviceable o rings / shutt off valve / plungers complete all as specified and directed. 24 s&f in replacement of control assembly fordg set capacity40 to 200 kvawith necessary modification to controll wiring, replacement of controll relays, programming with all the parameters for safety protection and running suitable for the existing dg sets. . 25 s&f in replacement of necessary control wiring for making the auto / manual mode condition of the existing dg sets 40 to 200 kva complete all as specified and directed. 26 s&f in replacement ofautomatic voltage regulator ( avr ) suitable for dg set of 40 kva to 200 kva capacity including taking out old unserviceable avr and making all connection, testing for smooth operation complete all as specified and directed. 27 s&f in replacement of magnetic pickup sensor suitable for 40 200 kva of exist makedg set connecting with panel circuit, starting and testing on load complete all as specified and directed. 28 s&f in replacement of oil pressure sensor suitable for 40 200 kva of make exist dg set connecting with panel circuit, starting and testing on load complete all as specified and directed. 29 s&f in replacement of coolant tempetaruresensor suitable for 40 200 kva of make exist dg set connecting with panel circuit, starting and testing on load complete all as specified and directed. 30 dismantaling the unserviceable radiator from dg set of capacity 40 to 200 kva of exist make andtransporting to contractors workshopfor locating the fault and overhauling & cleaning using air compressor, de scaling with acid, removal of leakage including soldering and welding, brazing as required and renewal of gaskets, nuts, bolts, mounting pads, hoses, clamps, clips, etc. and refixing / reassembling its original position after making proper connections, aligning, testing including transporting back the same to site complete all as specified and directed.note : the rates quoted by the contractor shall deemed to include thereplaced spares / parts, transportation cost from site of installation to contractors repair workshop and back. 31 cleaning of diesel tank of various capacity dg set inside / out side oftank complete with drain out dhpp ( n ) and cleaning tank and applying two coats of synthetic enamel paint ( 1st grade quality ) on out side of tank including necessary weldings and refilling the dhpp ( n ) & testing complete all as specified and directed. 32 s&f in repairs of electronic timers with auxilary voltage of 110 / 240 / 415v 50hz for operation of 12 120 secs complete all as specified and directed. 33 s&f in repairs of speed control units 40 to 200 kva dg stes of exist makecomplete all as specified and directed. 34 s&f in repairs auxilary control contactors side mounting add ons ( 1no+1nc ) as per existing capacity at respective site complete all as specified and directed. 35 s&f in replacement of new power contactor of capacity 360 amp 4 pole, 415 volts with side mounting, mcx type auxilary contacts operable at 220 v, 50hz including taking down ofdefective power contactor from amf panel complete all as specified and directed. 36 s&f in replacement of 3 phase digital multi function meter with suitable accessories and fixing arrangements complete all as specified and directed. 37 s&fin replacement of selector switch suitable for 415 volts complete all as specified and directed. 38 s&fin replacament of led type phase indicator to be fitted on panel ( r, y , b as per site requirement ) as per existing model / capacity including taking down of old unserviceable one complete all as specified and directed. 39 s&f in replacment of digital typevoltmeter 0 500volts with selector switch, 3 phase, complete all as specified and directed. 40 s&f in replacment repairs of digital type ammeter 0 200 / 300 amps with 3 nos ct coils and selector switch, 3 pohase complete all as speicified and directed. 41 s&f in replacement for alarm system with complete wiring complete all as specified and directed. 42 s&f in replacment of dg setdoor lock and key assembly suitable for exit dg set doors as per existing model complete all as specified and directed. 43 removal of rusted ms sheet at any portion of canopy and supply and fixing of 3.15 mm thick ms sheet of size 300 mm x 300 mm with fitting / welding as specified and directed. 44 m&l forpainting two coats of synthetic enamel paint of existing colour at site over a coat of red oxide primer for dg sets complete body surfaces complete all as specified and directed. 45 m&l for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick, burried directly in ground ( earth pit not less than 2.25 meters deep below ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised earth lead by means of bolts, nuts, check nuts and washer of galvanised iron strip 32 x 6mm as earth lead as shown in electrical plate no. 3 of ssr part i connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft / loose soil, returning filling, disposal od surplus soil, earth pit in pcc 1:3:6 type c 1 using 20mm graded crushed stone aggregate pit, funnel, 20mm bore gi tubing medium grade for watering pipe, 40mm bore medium grade gi pipe for protection of gi earth strip and pre cast earth pit cover 50mm thick made of rcc ( 1:1.5:3 ) type a1 duly reinforced with 8mm dia tmt bar @ 100 mm c / c both ways, one lifting handle made out of 10mm dia tmt bar 250mm long embedded in cover slab and cover, wire, copper lugs etc mesh, charcoal and common salt in alternate layer of 15 cm thick including taking down old unserviceable one complete all as specified and directed. 46 repair of earth pit including required exacavation, earth work and pcc work to make good damaged / disturbed surfaces of earth pit chamber & making new pit cover of rcc 1:2:4 type b 1 using 20mm graded crushed stone aggregate reinforced and lifting handle on rcc cover with 8mm ms bars at 150 mm centre to centre both ways including supply & fixing of wire mesh and funnel including re connection of earth wire / strip with panel / transformer using gi nut, bolts & washer complete all as specified & directed 47 m&l for repair / maint / overhauling long travel mechanism with lubrication lt wheel & gear box, over hauling hoist mechanism with reduction gear box, over hauling cross travel mechanism with gear box, testing & commissioning 5 ton eot crane, replacement of defective any minor parts complete all as specified and directed. 48 m&l for painting of complete eot crane with golden yellow colour paint including writing letters or figures ( block, roman, italic or indian ) n exc. 30 cm high with synthetic enamel paint as per colour scheme all as specified ( make rockwell ) 49 m&l for replacement of pvc flexible cable 1.5 sqmm 16 core copper wire complete all as specified and directed. 50 m&l for replacement of rotary geard limit switch ratio 48:1 complete all as specified and directed. 51 m&l for replacement of lever type limit switch complete all as specified and directed. 52 m&l for replacement of e.m brake ( 200mm ) coil 415v, ac complete all as specified and directed. 53 m&l for replacement of lubrication gear oil no.68 complete all as specified and directed. 54 m&l for replacement of current collector shrouded busbar type complete all as specified and directed. 55 m&l for replacement of 3 pole power contactor type ml4 type complete all as specified and directed. 56 m&l for replacement of hydraulic thrustor brake 300mm 34kg complete all as specified and directed. 57 m&l in replacement of damage ct shaft made out of en8 material medium carbon steeloff size in 80mm x 500mm with various step and key way slot 12mm both side on shaft complete all as specified and directed. 58 m&l in replacement of spherical roller bearing off suitable size complete all as specified and directed. 59 comprehensive maintenance inclding preventive and periodical maintenane and servicing of ro systems complete 03 nos, i.e.500 lph 01 no & 2000 lph 02 nos capacity. make of eukawa & ion exchange with connected motors, upvc pipe lines, butterfly valves, multi port valves etc, respectively, including servicing / cleaning of all filters / back wash etcin reliable safe and efficient condition through oem by periodically examining, preventive maintenance of plants, pipe lines, valves for trouble free function as per recommendation and attending breakdown / complaint as and when on required basis, maintenance on regular basis complete with preventive maintenanceincluding replacement of upvc pipes ( different sizes ) short lengths upto 5 mtrs, fittings, flanges with nut and bolts, pressure gauges, replacement of required necessary fittings alongwith rectification of defects complete all as specified and directed.all as directed. notes : ( i ) the contractor shall carry out routine checking of the complete plants and rectify the any defects noticed immediately ( iii ) treated water tds should be maintained less than 100mg / l and as directed, submit he monthly water test report of treated water. ( iv ) the rates quotedagainst for this item shall be applicable for a period of 01 month. ( v ) rates quoted aginst the above mentioned work wise items are required of efficient working of plant are to be included in the job . ( vi ) unserviceable and consumable parts will be measured and paid seperately unde relevent items as mention in below. ( vii ) if complaints were not rectified within 04 hrs of intimation, the following penalities will be imposed and deducted from contractors dues : ( a ) rs 1500 / per complaint for not attending the complaint and keeping pendig 04 hrs to 12 hrs / per complaint. ( b ) rs 3000 / per complaint for not attending the complaint and keeping 12 hrs to 24 hrs / per complaint. 60 replacement in repairs membrane high pressure, 500 lph.make dow / hydronautics / csm 61 replacement in repairs membrane high pressure, 2000 lph.make as per sample 62 replacement in repairsfor sediment ( sand and silt ) , dirt and rust particles, high efficiency, low pressure drop, removal up to 5 micron filter cartridges suitable 500& 2000lph capacity makes as per existing all as specified and directed. 63 replacement media in sand filter ( gravel, pebbles & fine sand ) complete all as specified and directed. 64 replacement activated carban in barban filter complete all as specified and directed. 65 supply only ro antiscalent high ph for membrane cleaner / water treat ment chemical complete all as specified and directed. 66 replacement in repairs rotameter suitable for 500 / 2000lph capacity ro system. make as per sample. 67 replacement in repairs of upvc pipe 20 to 40 mm dia with fitting complete suitable for ro systemas per sample. 68 replacement in repairs of membrane housing suitable for 500 lph capacity ro system of eukawa make .as per sample 69 replacement in repairs of membrane housing suitable for 2000 lph capacity ro system of ion exchange make .as per sample 70 replacement in repairs of housing bowl suitable for 500 & 2000 lph capacity ro system, make .as per sample. 71 replacement in repairs of lt relay, 230v ac supply suitable for 500 & 2000 lph capacity ro systemmake .as per sample. 72 s&f in reapirs of multi port valves fixing at sand filter and carbon filter vessles all as specified and directed. makes as per sample. 73 s&f, testing and commissioning high pressure pumps for ro plant, vertical type having speed 2780 rpm, 230 v, 2hp, class f insulation, eff 76% complete with fixing necessary accessories including taking down old unserviceable deposit to store yard complete all as specified and as directed. make : cri / crompton / kirloskar. 74 s&f, testing and commissioning self priming regenrative pumps for ro plant, mini star model having speed 2780 rpm, 230 v, 1hp, class b insulation, size 25x25mm, head 6 45 mtrs, dis range 50 lpmwith fixing necessary accessories incl taking down old unsv deposit to store yard complete all as specified and as directed. make : cri / cropmton / kirloskar. 75 s&f in repairs for rotational moulded polyethylene water storage tanks100 ltrs capacity ( cylindrical vertical with closed top in white colour transparent type for using antiscaling chemicals for ro plants ) hoisted and fixed in position all as specified and directed. 76 m&l for disconnection electrical and water connection of the raw water feed monoblock pumpset with motor and base plate and transporting to work shop opening carefully and rewinding the burnt out winding, replacement of bushes, gland packing, ball bearing, rubber gasket nut and bolt and replacing the required spares parts as per existing complete re fixing its in original position and making out all electrical and water connection and testing complete all as specified and directed for the size / capacity of motors upto3 hp.note : rate includes transportation of motor from the place of installation for repairing and reinstalling the same on existing foundation & testing & commisioning. 77 m&l for disconnection electrical and water connection of the high presuure feed pump, multi stage centrifugal type and transporting to work shop opening carefully and rewinding the burnt out winding, replacement of bushes, gland packing, ball bearing, rubber gasket nut and bolt and replacing the required spares parts as per existing complete re fixing its in original position and making out all electrical and water connection and testing complete all as specified and directed for the size / capacity of motors upto3 hp.note : rate includes transportation of motor from the place of installation for repairing and reinstalling the same on existing foundation & testing & commisioning. 78 s&f in repairs for antiscalant dosing unit capacity upto 6 lph @ 3.5 bar including inlet and outlet flexible pvc pipes all as specified and directed. 79 s&f in repairs pressure gauges for monitoring of flow meters all as specified and directed. ( makes as per sample ) 80 testing of treated water of stp and submission of detailed test report to the office of the engr in charge and testing in govt approved laboratory as approved. ( a ) carrying out minimum essential testing of water as per is 3025mandatory for chemical, odour, ph value tss bod cod residual chlorine total nitrogen, sulphate, oil and grease ammonical nitrogen ( nh3 n ) and bacteriological total collifrom organisms as below: rest of the characterstied of the treated water shall be as per is : 3025note 1 rate quoted shall deemed to be included for : ( i ) cost of sterilised bottle as required ( ii ) to and fro transportation charges for collection of sample 81 ( i ) tss: < 10 mg / ltrs 82 ( ii ) bod : < 10 mg / ltrs 83 ( iii ) cod :< 150 mg / ltrs 84 ( iv ) ph : 6.5 8.5 85 ( v ) total coliform : , < 100 mpn / 100 ml ( desired nil ) 86 ( vi ) residual ci > 1 mg / ltr 87 rest of the characterstied of the treated water shall be as per is : 3025 88 note 2 rates quoted shall deemed to be included for : 89 ( i ) cost of sterilised bottle as required 90 ( ii ) to and from transportation charges for collection of sample 91 note 3 in case contractor fails to provide monthly test report, a penalty of rs 3000 / per test report shall be recovered from the contractor dues. 92 testing of sewage sludge water as per revlevant is of stp and submission of detailed test report to the office of the engr in charge and testing in govt approved laboratory as approved by ge ( a ) carrying out minimum essential testing of sewage water as per revlevant is mandatory for chemical, odour, ph value tss bod cod total nitrogen, sulphate, oil and grease ammonical nitrogen ( nh3 n ) and bacteriological total collifrom organisms and other charaterstics as per relevant is of sewage water: note 1 rates quoted shall deemed to be included for : ( i ) cost of sterilised bottle as required ( ii ) to and fro transportation charges for collection of sample 93 supply & mixing of sodium hypo choloride having 10% content complete all as specified and directed. 94 supply & mixing of poly aluminium choloride 100% purity complete all as specified and directed. 95 supply & mixing of poly electrolite 100% purity complete all as specified and directed. 96 supply & filling compressor oil 460 complete all as specified and directed. 97 material and labour in replacement of quartz silica sand 32 64 grade complete all as specified and directed. 98 material and labour in replacement of quartz silica sand 16 32 grade complete all as specified and directed. 99 material and labour in replacement of quartz silica sand 8 16 grade complete all as specified and directed. 100 material and labour in replacement of quartz silica sand 4 8 grade complete all as specified and directed. 101 material and labour in replacement of activated carbon iv 1000 complete all as specified and directed. 102 material and labour in replacement of feb ( mbbr ) media suitable for stp make as per sample. 103 taking out complete pebbles from the bottom upto the depth of 0.6 mtr of the filter of size 1800 mm dia and 2300 mm height and refilling the same pebbles after washing and cleaning thoroughly. 104 periodical cleaning of sewage well as capacity ( upto 5mtrs dia and 9 mtrs depth ) cum and removing of settle down sewage sludge cum mud / de silting etc. all as required at site anddirected atanand parbat mil stn ( klp location, map ph i ) and cod area. note: the rate quoated by the tenderer is deemed to be included in the unit rate of the following : 105 diesel driven pump set of appropriate capacity not less than 5 / 7.5 hp with operatorincluding necessary pol required at site for de watering of sewage septic water including pvc heavy duty flexible hose pipe for suction and delivery purposes 106 tractor mountedstorage tank of appropriate capacity not less than 1 kl with driver directly collected from the soak well and disposing the same to the location out side of military contonement where as approved by pcb and also liase with delhi muncipal corporation board as directed. 107 tractor / truck with driver for disposal of sewage sludge and pol required for the same ( duly covered with necessary tarpaline ) and depositing the same to the location where approved by pcb or as directed.. 108 labour element and t&p required for removal of settled down sewage sludge / mud inside the sewage tank for scooping out from inside and below the septic / staining sewage water inside the well and lifting the same and deposited out side of military contonment and out side location as mentioned above. 109 appropriate qty of phenyle required at site for sterilization of sewage sludge being collected in the sewage tank and all as directed. 110 necessary oxygen mask, gloves, gum boot and all other safety aspects and including necessary phawda, steel bucket, manila rope etc. required at site and all as directed. 111 m&l for cleaning oftreated water tank atanand parbat at klp loaction stp of storage capacity of water 50000 gallons, filter feed tank of capacity 63 cum and chlorine contact tank of capacity 17 cum thoroughly by removing mud, grits etc from the tankby following method : 112 cleaning inner surface of tank complete by scraping with steel wire brush and and removing mud and sludge collected inside the tank manuallyat a distance not exceeding 50 mtr all as directed. 113 washing with clean water and bleaching powder mixture throughly complete tank internally and removel of left out sludge if any at site at a distance not exceeding 50mtr all as directed. 114 supply and laying including taking up galvanised steel water tubing medium grade isi marked screwed socketed joints complete with all tube fitting ( such as bends, elbow, tees, short pieces, connectors, back nuts, diminishing pieces, caps, plugs, threaded flanges and unions, etc ) and fixing complete with clips, wall hooks, wooden plugs, or laying in trenches, etc., also cutting, screwing and waste and for making forged bends on piping as required at site including taking down the existing pipe line with fitting etc of following sizes: 115 80 mm dia 116 50 mm dia 117 40 mm dia 118 supply and laying mild steel water tubing heavy duty with welded joints complete with all tube fitting ( such as bends, elbow, tees, short pieces, connectors, back nuts, diminishing pieces, caps, plugs, flanges and unions, etc ) and fixing complete with clips, wall hooks, wooden plugs, or laying in trenches, etc., also cutting, screwing, welding and waste end for making forged bends on piping as required at site including taking down the existing pipe line with fitting etc of following sizes: 119 40 mm dia 120 50 mm dia 121 80 mm dia 122 100 mm dia 123 supply and fixingbutterfly valves iron body screwed down high pressure with iron wheel head / long shank and cup butterfly type screwed both ends for iron pipe including taking out unserviceable valve for the following sizes: 124 40 mm dia 125 50 mm dia 126 80 mm dia 127 m&l for spray painting two coats of synthetic enameled paint of specified colour after preparation of surface and writing letters and numbers complete of complete sewage treatment plant capacity 100 cum / day with equalization tank, raw sewage pumps, mbbr reactor, chlorine tank, filter feed pump, dual media filters, rcc treated water tank, treated filter pumps, sludge drying beds, oil free blowers and accessories complete all as specified and directed. 128 m&l for disconnection electrical and water connection of the monoblock pumpset with motor and base plate and transporting to work shop opening carefully and replacement of winding, bushes, gland packing, ball bearing, rubber gasket nut and bolt and replacing the required spares parts as per existing complete re fixing its in original position and making out all electrical and water connection and testing complete all as specified and directed for the size / capacity of motors upto7.5 hp.note : rate includes transportation of motor from the place of installation for repairing and reinstalling the same on existing foundation & testing & commisioning. 129 m&l for disconnection electrical and water connection of the compressors and transporting to work shop opening carefully and replacement of spare parts bushes, gland packing, ball bearing, rubber gasket nut and bolt and replacing the required spares parts as per existing complete re fixing its in original position and making out all electrical and water connection and testing complete all as specified and directed for the size / capacity of up to 110 m3 / hr.note : rate includes transportation of compressor from the place of installation for repairing and reinstalling the same on existing foundation & testing & commisioning. 130 m&l for lifting / lowering of non clogging submersible pump and motor capacity up to 7.5 hpfrom sewage well after disconnecting electric and water connection of any make and any size capacity under any of chain pulley block or manually appropriate length upto 10m after opening the socket and pipe eplacement of winding, bushes, gland packing, ball bearing, thrust bearings, sand guard plate, gm impellers, rubber gasket nut and bolt and replacing the required spares parts as per existing complete re fixing its in original position and making out all electrical and water connection and testing complete all as specified and directed. 131 supply and fixing in reapirs of multi port valvesfixing at mediafilter vesselses for stpall as specified and directed. makes as per sample. 132 s&f in repairs for dosing unit capacity electronic metering pumps for chemiclas dosing system for stp incl inlet and outlet flexible pvc pipes all as specified and directed.makes as per sample 133 material & labour in repairs for cross arms, bracings, supports, clamps, angle iron, flats, ladders and back plates fabricated from ms structural steel sections including nuts, bolts and washers of suitable sizes including welding, bending ( cold or hot ) , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminum paint over one coat of red oxide primer, complete all as directed. 134 m&l for diamantling, opening of automatic voltage stabilizer 200 kva rating ( 300 480 volts ) , out put 415 v including disconnecting electric connectioncomplete all as specified & directed. 135 m&l for repairs taking up deemer assembly complete by carefully by manual chain pulley block and replaceemnt of burnt wiinding coil with existingsize and gauge of copper winding wire inclduing transportation charges from site to work shop and back complete all as specified & directed. 136 m&l for replacment of motor assembly for moving of 20 kg load complete all as specified & directed. 137 m&l for replacement of carbon brush ( 03 sets of 03 nos each ) complete all as specified & directed. 138 m&l for repair of internal wiring and servicing complete all as specified & directed. 139 m&l for in repairs machine pressed precast conctete interlocking paver block with grey cement and no pigment any shape and size confirming to is 15658 2006 of 60mm thickness, m 35 grade including sand filling including dismantling complete all as specified and directed. 140 demolition of pcc in ground floor and paving not exceeding 15 cm thickness ( below or above ground level ) complete all as specified & directed. 141 m&l for broken stone boulders hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15cm thick, wateredand rammed to a true surface including demolition complete all as specified and directed. 142 m&l for sand filling under floors or in foundations including watering and consolidation complete all as specified & directed. 143 shifting and relocating of trolley mounted transformer of any capacity and ratingin aor ( i.e. kwc camp mrs area toanand parbat mil stn mrs area ) outdoor type including removing and refixingnecessary cable connections complete all as specified and directed. note: ( i ) necesary t&p complete shall be arranged by the contractor. ( ii ) during shifting process damage to any existing infrastructure, the same is make good by his own cost. 144 taking up existing di pipe sewage water pumping system line 80 to 150mm bore including fittings and relaying, jointing and testing of same in to trenches in position after cleaning and removal of scale / blockage complete for the following sizes note earth work, lead joint and rubber tyton joints shall be measured and paid separately under relevant items : 145 material and labour for di specials of any size such as tees, bends of any sizeand radius, tapers, collers, tail pieces, caps and plugs etc incl takinng down unsv complete all as specified. 146 m&l for rubber gasket joint ( tyton joint ) with jointingmaterial for di pipe of 80 to 150mm bore including taking down unserviceable complete all as specified and directed. 147 material & labour for earthing with galvanised steel earth plate electrode 60cmx 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer ofcharcoal dust and common salt filling in alternate layers and electrode connections by usinggalvanised iron strip of size 32 x 6 mm as earthing lead ( upto the body ofthe equipment ) by means ofbolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm diagi pipe connected to main switch board or main control board and gi pipe medium grade 20mm bore for watering and including funnel , wire mesh , rcc pit cover and pcc chamber pit with pcc ( 1:3:6 ) type c 2 using 40mm graded crushed stone aggregate, including excavation and earth work in any type ofsoil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate no 5 ofssr 1991 ( part i ) including testing on completion if desired earth resistance is not obtained the earthing will be redone without extra cost complete all as specified anddirected. 148 s&f earth continuity conuctor or main earth lead fixed to wall on batten or recess or chess or buried in ground drawn in conduit / pipe or fixed to the pole or any other situation for loop earthing etc as required32x6 mm dia galvanised iron strip all as per specified and directed....

Indian Air Force - Delhi

35538214 procurement of ttge spares for mirage 2000 aircraft memory card p nose rear assembly valve beam, equipped sensor incident base, voltag e regulator adapter, squ are drive, male1 / 2, female 3 / 8 box head rear assembly navigation box ( h ) alternator control assy push pull cross beam sfgblock, conne ction pressure regulator agb attachment assambly ( lh ) hooking system power supply seat chute packing press relay 1 reversing switch electrical unit=> limited...